Scorriton STW

Spill evidence · Friends of the Dart

Scorriton STW

Storm overflow at the works · SBB01058 · feeds SCORRITON_STW_SCORRITON
Dry spill

Evidence strength

High confidence
  • Dry across a 4-day antecedent window
  • Rain gauge close (≤5 km)
  • Monitor 100% operational that year
  • Short discharge (<1 h) — weaker signal

The discharge

Spill day
Monday, 21 March 2022
Started
21 Mar 2022, 18:35
Ended
21 Mar 2022, 19:13
Duration
38 minutes
Receiving water
Dart
Parish
West Buckfastleigh

Rainfall evidence

Daily rainfall at the matched gauge (Holne Priddons Farm) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Dry spill4-day window: Dry spill
DateRainfall
21/03/2022 (spill day)0 mmdry
20/03/20220 mmdry
19/03/20220 mmdry
18/03/20220 mmdry
17/03/20220 mmdry

River flow that day: 8.969 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 2.0 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
EA annual return (2022)
107 counted spills · 891 h total
Monitor uptime (2022)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB01058). Rainfall: EA Hydrology gauge b000c3f6-3922-48ea-8726-4173de4998d0. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Hub.